DONGGUAN YUYANG INSTRUMENT CO., LTD

Manufacturer from China
Verified Supplier
8 Years
Home / Products / Electrical Test Set /

Current And Potential Transformer Test Set CT PT Analyzer

Contact Now
DONGGUAN YUYANG INSTRUMENT CO., LTD
Visit Website
City:dongguan
Province/State:guangdong
Country/Region:china
Contact Person:MrAnson
Contact Now

Current And Potential Transformer Test Set CT PT Analyzer

Ask Latest Price
Video Channel
Brand Name :YUYANG
Model Number :CPT-I
Certification :CE
Place of Origin :China
MOQ :1 Set
Price :USD9300
Supply Ability :100 sets per month
Delivery Time :15 days
Packaging Details :Plywood case
Keyword :CT PT Analyzer
Test standard :IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supply :AC220V±10%, 50/60Hz±10%
Display :LCD touch screen
Memory capacity :>1000 groups
Software :English
Test object :ct and pt
Warranty :1 Year
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Electrical Current and Potentional Transformer Test Set CT PT Analyzer

Test for current transformer:

  • Excitation curve and parameters test

  • Turns ratio test

  • Ratio and phase error test

  • Polarity mark check

  • Winding resistance measurement

  • Secondary loop burden measurement

  • Error line curve test for protection CT

  • Transient CT parameters test

  • CT nameplate guess

  • Saturation hysteresis loop curve measurement

  • Tests for Potencial Transformer:

  • Turns ratio test

  • Ratio error and phase angle error test

  • Polarity test

  • Secondary burden test

  • Winding resistance test

Test for Potential Transformer

  • Secondary burden test

  • Winding resistance test

  • Polarity test

  • Turns ratio test

  • Ratio error and phase angle error test

Applications of CT/ PT Analyzer:

  • CT nameplate check

  • CT parameters check in work burden

  • CT transient parameters analysis

  • CT ratio and phase error calibration

  • PT routine test

Specifications:

Item Name Current Transformer CT and PT Potential Transformer Tester
Test standards IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supply AC220V±10%, 50/60Hz±10%
Voltage output 0.1~180V (AC)
Current output 0.001~5A(RMS)
Power output 500VA
Max. knee voltage measurement 45KV
Current measurement
Range 0~10A (automatically change range in 0.1/0.4/2/10A)
Error <±0.1%+0.01%FS

Voltage measurement Range 0~200V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%FS
Turns ratio measurement Range 1~35000
1~2000, error<0.05%
2000~5000,error<0.1%
5000~35000,error<0.2%
Phase measurement error ±2min
resolution 0.01min
Winding resistance measurement
Range 0~8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm)
Error < 0.2%RDG+0.02%FS
Maximum resolution : 0.1mΩ
Temperature measurement -50~100 Celsius degree; error<3 Celsius degree
CT Secondary burden Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution : 0.001ohm


PT Secondary burden
Error 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Maximum <0.2%RDG+0.02%FS
resolution 0.1ohm

PT ratio measurement

Range
1~35000
1~10000 error<0.1%
10000~35000 error<0.2%
PT ratio error measurement :Typical error<0.05%,
Maximum Error<0.1%
PT phase angle measurement maximum error < 3min
Make evaluation for test results according to selected standards
Make word report for test result
Make word reports one time for multi-group test records on the PC
Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
Compare excitation curves with saved excitation curves in the same window
Memory capacity >1000 groups test results
Working condition temperature -10℃~50℃; moist ≤90%

Current And Potential Transformer Test Set CT PT AnalyzerCurrent And Potential Transformer Test Set CT PT Analyzer

Inquiry Cart 0